BuyLog Flippingbook FEB 2025
9-43
DISCONNECT SWITCHES AND OPERATING MECHANISMS, BUYLOG SECTION 9
— Non-fusible disconnect switches OT160, UL Technical data for non-fusible disconnect switches
Technical data according to UL98, CSA C22.2 No.4 Switch type
OT160G c UL us Listed
UL Recognized
100 A
125 A
General purpose amp rating max. operating voltage
pf=0.7…0.8
-40° to 40 °C
600 V
600 V
240 Vac
40 HP/104 A
40 HP/104 A
pf=0.4…0.5 Three phase
480 Vac
75 HP/96 A
75 HP/96 A
600 Vac
100 HP/99 A
100 HP/99 A
Max. horsepower rating/motor FLA current
240 Vac
20 HP/88 A
20 HP/88 A
Single phase
480 Vac
30 HP/66 A
30 HP/66 A
250 Vdc
20 HP/60 A
20 HP/60 A
J
150 A/100 kA
150 A/100 kA
Fuse type
Fuse size/short circuit rating
T
150 A/100 kA
150 A/100 kA
RK5
60 A/100 kA
60 A/100 kA
Endurances Min. electrical endurance, pf. 0.75 - 0.8
6,000 Oper. cycles
6,000 Oper. cycles
Mechanical endurance
20,000 Operations
20,000 Operations
Terminal lug kits
integrated
integrated
Wire range
Use copper conductors only
60-75 °C
AWG 8-1/0
AWG 8-1/0
Torque
Wire tightening
53 lb.in
53 lb.in
3-pole switch
0.5 lb
0.5 lb
Weight without accessories
4-pole switch
0.6 lb
0.6 lb
400 x 600 x 230 mm
–
Minimum enclosure dimensions
Height x width x depth
15.75 x 23.62 x 9.06 in
–
Made with FlippingBook Online newsletter creator