BuyLog Flippingbook FEB 2025

9-43

DISCONNECT SWITCHES AND OPERATING MECHANISMS, BUYLOG SECTION 9

— Non-fusible disconnect switches OT160, UL Technical data for non-fusible disconnect switches

Technical data according to UL98, CSA C22.2 No.4 Switch type

OT160G c UL us Listed

UL Recognized

100 A

125 A

General purpose amp rating max. operating voltage

pf=0.7…0.8

-40° to 40 °C

600 V

600 V

240 Vac

40 HP/104 A

40 HP/104 A

pf=0.4…0.5 Three phase

480 Vac

75 HP/96 A

75 HP/96 A

600 Vac

100 HP/99 A

100 HP/99 A

Max. horsepower rating/motor FLA current

240 Vac

20 HP/88 A

20 HP/88 A

Single phase

480 Vac

30 HP/66 A

30 HP/66 A

250 Vdc

20 HP/60 A

20 HP/60 A

J

150 A/100 kA

150 A/100 kA

Fuse type

Fuse size/short circuit rating

T

150 A/100 kA

150 A/100 kA

RK5

60 A/100 kA

60 A/100 kA

Endurances Min. electrical endurance, pf. 0.75 - 0.8

6,000 Oper. cycles

6,000 Oper. cycles

Mechanical endurance

20,000 Operations

20,000 Operations

Terminal lug kits

integrated

integrated

Wire range

Use copper conductors only

60-75 °C

AWG 8-1/0

AWG 8-1/0

Torque

Wire tightening

53 lb.in

53 lb.in

3-pole switch

0.5 lb

0.5 lb

Weight without accessories

4-pole switch

0.6 lb

0.6 lb

400 x 600 x 230 mm

Minimum enclosure dimensions

Height x width x depth

15.75 x 23.62 x 9.06 in

Made with FlippingBook Online newsletter creator