BuyLog Flippingbook FEB 2025
DISCONNECT SWITCHES AND OPERATING MECHANISMS, BUYLOG SECTION 9
9-42
— Non-fusible disconnect switches OT16...100, UL Technical data for non-fusible disconnect switches
Technical data according to UL/CSA, AC ratings Switch type OT16F
OT25F
OT40F
OT63F
OT80F
OT30F
OT60F
OT100F
C UL US Listed C UL US Listed C UL US Listed C UL US Listed C UL US Listed C UL US Listed
C UL US Listed
C UL US Listed
-
-
Approval
E63822
E63822
E63822
E63822
E63822
E101914 E101914 E101914
UL508
UL508
UL508
UL508
UL508
UL98
UL98
UL98
-
-
Compliance
CSA C22.2 No.14
CSA C22.2 No.14
CSA C22.2 No.14
CSA C22.2 No.14
CSA C22.2 No.14
CSA C22.2 No.4
CSA C22.2 No.4
CSA C22.2 No.4
General purpose amp rating Max. operating voltage
pf = 0.7...0.8 -40° to 40 °C 20A
30A
40A
60A
80A
30A
60A
100A
-
-
600V
600V
600V
600V
600V
600V
600V
600V
5 HP/ 15.2A 10 HP/ 14.0A 10 HP/ 11.0A
7.5 HP/ 22.0A 15 HP/ 21.0A 20 HP/ 22.0A 1.5 HP/ 20.0A
10 HP/ 28.0A 20 HP/ 27.0A 25 HP/ 27.0A 2 HP/ 24.0A 5 HP/ 28.0A 10 HP/ 26.0A 15 HP/ 27.0A
15 HP/ 42.0A 30 HP/ 40.0A 30 HP/ 32.0A 7.5 HP/ 40.0A 15 HP/ 34.0A 15 HP/ 27.0A 2 HP/ 24.0A
20 HP/ 54.0A 40 HP/ 52.0A 40 HP/ 41.0A 10 HP/ 50.0A 20 HP/ 44.0A 20 HP/ 38.5A 2 HP/ 24.0A
10 HP/ 28.0A 20 HP/ 27.0A 30 HP/ 32.0A
20 HP/ 54.0A 40 HP/ 52.0A 40 HP/ 41.0A
30 HP/ 80.0A 50 HP/ 65.0A 50 HP/ 52.0A 15 HP/ 68.0A 25 HP/ 55.0A 20 HP/ 35.0A 5 HP/ 56.0A
240V
Three phase, pf = 0.4...0.5
480V
600V
Max. horsepower rating/motor FLA current
1 HP/ 16.0A 2 HP/ 12.0A 5 HP/ 14.0A
2 HP/ 24.0A 5 HP/ 28.0A
3 HP/ 34.0A
120V
3 HP/ 17.0A
7.5 HP/ 40.0A
240V
Single phase
7.5 HP/ 21.0A 10 HP/ 20.0A
480V
-
-
7.5 HP/ 16.0A
600V
-
-
Maximum fuse size
-
30A 60A 30A 60A 30A 60A 100A 150A 100A 150A 60A
60A
150A 100A
100 kA 100 kA
100 kA 100 kA
200 kA 200 kA
Fuse type J
10kA 10kA 10kA 10kA 10kA 10kA
-
-
200kA
200kA
50kA
Fuse type T
10kA 10kA 10kA 10kA 10kA 10kA
-
-
200kA
200kA
50kA
Short circuit rating with fuse
Fuse type
RK1
10kA -
10kA -
10kA -
-
-
-
-
-
-
-
-
5kA 5kA 5kA 5kA 5kA 5kA 10kA 5kA 10kA 5kA -
-
-
-
Fuse type
RK5 1
Fuse type L
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Fuse type H
-
-
-
-
-
-
-
5kA
-
5kA
-
-
-
-
Endurances Min. electrical endurance, pf. 0.75...0.8 Mechanical endurance Terminal lugs
-
-
6,000 Oper. 6,000 Oper. 6,000 Oper. 6,000 Oper. 6,000 Oper. 6,000 Oper.
6,000 Oper.
6,000 Oper.
-
-
20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper.
-
-
integrated integrated integrated integrated integrated integrated integrated integrated
Copper wire range -
60-75 °C AWG 18-8 AWG 18-8 AWG 18-8 AWG 14-4 AWG 14-4 AWG 14-4 AWG 14-4 AWG 8-1/0
0.8 Nm / 7 lb-in
0.8 Nm / 7 lb-in
0.8 Nm / 7 lb-in
2 Nm / 18 lb-in
2 Nm / 18 lb-in
6.2 Nm / 55 lb-in
6.2 Nm / 55 lb-in
6.2 Nm / 55 lb-in
Wire tightening
Torque
-
1 Fuse size 70A for RK5
Made with FlippingBook Online newsletter creator