BuyLog Flippingbook FEB 2025

DISCONNECT SWITCHES AND OPERATING MECHANISMS, BUYLOG SECTION 9

9-42

— Non-fusible disconnect switches OT16...100, UL Technical data for non-fusible disconnect switches

Technical data according to UL/CSA, AC ratings Switch type OT16F

OT25F

OT40F

OT63F

OT80F

OT30F

OT60F

OT100F

C UL US Listed C UL US Listed C UL US Listed C UL US Listed C UL US Listed C UL US Listed

C UL US Listed

C UL US Listed

-

-

Approval

E63822

E63822

E63822

E63822

E63822

E101914 E101914 E101914

UL508

UL508

UL508

UL508

UL508

UL98

UL98

UL98

-

-

Compliance

CSA C22.2 No.14

CSA C22.2 No.14

CSA C22.2 No.14

CSA C22.2 No.14

CSA C22.2 No.14

CSA C22.2 No.4

CSA C22.2 No.4

CSA C22.2 No.4

General purpose amp rating Max. operating voltage

pf = 0.7...0.8 -40° to 40 °C 20A

30A

40A

60A

80A

30A

60A

100A

-

-

600V

600V

600V

600V

600V

600V

600V

600V

5 HP/ 15.2A 10 HP/ 14.0A 10 HP/ 11.0A

7.5 HP/ 22.0A 15 HP/ 21.0A 20 HP/ 22.0A 1.5 HP/ 20.0A

10 HP/ 28.0A 20 HP/ 27.0A 25 HP/ 27.0A 2 HP/ 24.0A 5 HP/ 28.0A 10 HP/ 26.0A 15 HP/ 27.0A

15 HP/ 42.0A 30 HP/ 40.0A 30 HP/ 32.0A 7.5 HP/ 40.0A 15 HP/ 34.0A 15 HP/ 27.0A 2 HP/ 24.0A

20 HP/ 54.0A 40 HP/ 52.0A 40 HP/ 41.0A 10 HP/ 50.0A 20 HP/ 44.0A 20 HP/ 38.5A 2 HP/ 24.0A

10 HP/ 28.0A 20 HP/ 27.0A 30 HP/ 32.0A

20 HP/ 54.0A 40 HP/ 52.0A 40 HP/ 41.0A

30 HP/ 80.0A 50 HP/ 65.0A 50 HP/ 52.0A 15 HP/ 68.0A 25 HP/ 55.0A 20 HP/ 35.0A 5 HP/ 56.0A

240V

Three phase, pf = 0.4...0.5

480V

600V

Max. horsepower rating/motor FLA current

1 HP/ 16.0A 2 HP/ 12.0A 5 HP/ 14.0A

2 HP/ 24.0A 5 HP/ 28.0A

3 HP/ 34.0A

120V

3 HP/ 17.0A

7.5 HP/ 40.0A

240V

Single phase

7.5 HP/ 21.0A 10 HP/ 20.0A

480V

-

-

7.5 HP/ 16.0A

600V

-

-

Maximum fuse size

-

30A 60A 30A 60A 30A 60A 100A 150A 100A 150A 60A

60A

150A 100A

100 kA 100 kA

100 kA 100 kA

200 kA 200 kA

Fuse type J

10kA 10kA 10kA 10kA 10kA 10kA

-

-

200kA

200kA

50kA

Fuse type T

10kA 10kA 10kA 10kA 10kA 10kA

-

-

200kA

200kA

50kA

Short circuit rating with fuse

Fuse type

RK1

10kA -

10kA -

10kA -

-

-

-

-

-

-

-

-

5kA 5kA 5kA 5kA 5kA 5kA 10kA 5kA 10kA 5kA -

-

-

-

Fuse type

RK5 1

Fuse type L

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Fuse type H

-

-

-

-

-

-

-

5kA

-

5kA

-

-

-

-

Endurances Min. electrical endurance, pf. 0.75...0.8 Mechanical endurance Terminal lugs

-

-

6,000 Oper. 6,000 Oper. 6,000 Oper. 6,000 Oper. 6,000 Oper. 6,000 Oper.

6,000 Oper.

6,000 Oper.

-

-

20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper. 20,000 Oper.

-

-

integrated integrated integrated integrated integrated integrated integrated integrated

Copper wire range -

60-75 °C AWG 18-8 AWG 18-8 AWG 18-8 AWG 14-4 AWG 14-4 AWG 14-4 AWG 14-4 AWG 8-1/0

0.8 Nm / 7 lb-in

0.8 Nm / 7 lb-in

0.8 Nm / 7 lb-in

2 Nm / 18 lb-in

2 Nm / 18 lb-in

6.2 Nm / 55 lb-in

6.2 Nm / 55 lb-in

6.2 Nm / 55 lb-in

Wire tightening

Torque

-

1 Fuse size 70A for RK5

Made with FlippingBook Online newsletter creator