BuyLog Flippingbook FEB 2025
LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
8-156
— Power Break ™ II circuit breakers Trip unit characteristics
Additional Features and Characteristics Exclusive to the Enhanced MicroVersaTrip ™ PM Trip Unit 1
Trip Unit Suffix M (Metering)
Function
Description
P (Relaying)
PM (Metering & Relaying)
Communications Amperes (A, kA) 2
POWER LEADER Communications Bus Link
STD STD
STD STD
STD STD
Selectable Phase Current ±2.5%
• • • • • •
• • • • • •
Voltage (V)
L-L or L-N Volts ±1.5%
Energy (kWh, MWh, GWh) Real Power (kW/MW) Total Power (kVA/MVA)
Total Energy Usage on Brkr ±4%
L-L or L-N Power ±4% L-L or L-N Power ±4% Circuit Frequency ± 1Hz
Frequency (Hz)
Demand & Peak Demand (kW)
– Adjustable pickup 50-90% – Adjustable delay, 1-15 seconds OFF – Adjustable pickup, 110-150% – Adjustable delay, 1-15 seconds OFF – Adjustable pickup, 10-50% – Adjustable delay, 1-15 seconds OFF – Adjustable pickup, 10-50% – Adjustable delay, 1-15 seconds OFF – Adjustable pickup, 10-990 kW – Adjustable delay, 1-15 seconds OFF – Power Reversal Direction
•
•
Under Voltage Trip
•
•
Over Voltage Trip
•
•
Voltage Unbalance
•
•
Current Unbalance
• •
• •
Power Reversal
1 MicroVersaTrip PM ™ functions require 24 Vdc control power. 2 Ampere reading also standard on MicroVersaTrip Plus trip units.