LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8

— Power Break ™ II circuit breakers Trip unit characteristics

Power+ Trip Unit Characteristics

Long Time

Short Time

Frame Max. Ampere Rating

Sensor Rating Amperes) (S)

Envelope Size

Current Setting (C ) (Pick-Up) Multiple of Rating Plug Amperes (X)

Delay 1 (Seconds 4 Bands)

Pick-up (Multiple of Current Settings (C)

Delay (Seconds 3 Bands)

800

200, 400, 800 800, 1000, 1600

I 2 T in 1 .10, .21, .35

2000

1600 2000

0.5, 0.6, 0.7, 0.8, 0.9, 0.95 and 1.0

1.5, 2.0, 2.5, 3.0, 4.0, 5.0, 7.0, and 9.0

2000

2.4, 4.9, 9.8, 20

3000 2500, 3000

1000, 2000, 2500, 3000

I 2 T out 2 .10, .21, .35

4000 4000

4000

Power+ Trip Unit Characteristics (continued)

Ground Fault Pick-Up (Multiple of Sensor Ampere Rating)

Envelope Size

Adjustable Instantaneous Pick-Up without ST (Multiple of Rating Plug Amperes) (X)

Adjustable Instantaneous Pick-Up with ST (Multiple of Rating Plug Amperes) (X)

Delay 3 (Seconds 3 Bands)

1.5 thru 10.0 1.5 thru 10.0 1.5 thru 10.0

1.5 thru 15.0 1.5 thru 15.0 1.5 thru 15.0 1.5 thru 13.0 1.5 thru 9.0

0.20 thru 0.60 0.20 thru 0.60 0.20 thru 0.60 0.20 thru 0.37 0.20 thru 0.30

I 2 T in 4 .10, .21, .35

2000

I 2 T out 2 .10, .21, .35

3000 1.5 thru 10.0 4000 1.5 thru 9.0

Enhanced MicroVersaTrip ™ Plus and PM Trip Unit Characteristics

Long Time

Short Time

Sensor Rating Amperes) (S) 200, 400, 800 800, 1000, 1600

Envelope Size

Frame Max. Ampere Rating

Current Setting (C ) (Pick-Up) Multiple of Rating Plug Amperes (X)

Pick-up (Multiple of Current Settings (C)

Delay 2 (Seconds)

Delay (Seconds)

800

800

I 2 T in 1 0.40

1600 1600 2000 2000

2000

0.5 thru 1.0 in increments of 0.05

1.5 thru 9.0 in increments of 0.5

2.4, 4.9, 9.8, 20

2500 3000

1000, 2000, 2500

3000

I 2 T out 2 .10, .21, .35

3000 4000

4000 4000

Trip Unit Characteristics (continued)

Adjustable Instantaneous Pick-Up without ST (Multiple

Adjustable Instantaneous Pick-Up with ST (Multiple of Rating Plug Amperes) (X) 1.5 thru 15.0 in 0.5 increments 1.5 thru 15.0 in 0.5 increments 1.5 thru 15.0 in 0.5 increments 1.5 thru 13.0 in 0.5 increments 1.5 thru 9.0 in 0.5 increments

Ground Fault

High Range Instantaneous

Pick-Up (Multiple of Sensor Ampere Rating) 0.20 thru 0.60 in increments of 0.01 0.20 thru 0.60 in increments of 0.01 0.20 thru 0.60 in increments of 0.01 0.20 thru 0.37 in increments of 0.01 0.20 thru 0.30 in increments of 0.01

Envelope Size

(Multiple of Frame Short-Time Rating) (H)

Delay With l 2 T In Seconds

Delay 3 With l 2 T Out Seconds

of Rating Plug Amperes) (X) 1.5 thru 10.0 in 0.5 increments 1.5 thru 10.0 in 0.5 increments 1.5 thru 10.0 in 0.5 increments 1.5 thru 10.0 in 0.5 increments 1.5 thru 9.0 in 0.5 increments

800

1600

.44 at 200% of pick-up at lower limit of band

1.0

2000

.10, .21, .35

3000

4000

S = Sensor amp rating C = Long-time current setting (pick-up)

1 Time delay shown at 600% of current setting at lower limit of band. 2 Time delay shown at lower limit of each band. All pick-up tolerances are ± 10%. 3 Time delay shown at lower limit of each band. Ground fault pick-up not to exceed 1200 amperes. 4 Time delay shown at 200% of pick-up at lower limit of band.

H = Short-Time Rating X = Rating plug amps