BuyLog Flippingbook FEB 2025
MOLDED CASE CIRCUIT BREAKERS, BUYLOG SECTION 6
6-12
— Tmax XT circuit breakers for (AC) distribution
Molded case circuit breakers (MCCB)
XT3 225
XT4 250 3, 4 2
Frame Size
[A]
Poles
[No.]
3, 4
Rated voltage
(AC) 50-60Hz
[V]
480 V Δ 3
600
Versions
Fixed, Plug-in
Fixed ,Plug-in, Withdrawable
L 1
V 1
X
Interrupting ratings
N
S
N S H 1
240 V (AC) 480 V (AC)
[kA] [kA]
50 25 10
65 35 10
65 100 150 200 200 200 25 35 65 100 150 200
600Y/347 V (AC) [kA]
–
–
–
–
–
–
600 V (AC)
[kA]
–
–
18 22 25 50 65 100
[No. Operations]
25000
25000
Mechanical life
[No. Hourly operations]
240
240
3-poles 4-poles
[mm]/[in] [mm]/[in] [kg]/[lbs]
[105 x 70 x 150] / [4.13 x 2.75 x 5.90] [140 x 70 x 150] / [5.51 x 2.75 x 5.90]
[105 x 82.5 x 160] / [4.13 x 3.25 x 6.3] [140 x 82.5 x 160] / [5.51 x 3.25 x 6.3]
Dimensions - Fixed (Width x Depth x Height)
Fixed 3/4-poles
[1.7 - 3.37] / [2.1 - 4.63]
[2.5 - 5.51] / [3.5 - 7.72]
Plug-in (EF) 3/4-poles
[kg]/[lbs]
[3.24 - 7.14] / [4.1 - 9.04]
[4.19 - 9.24] / [5.52 - 12.17]
Weight
Withdrawable (EF) 3/4-poles
[kg]/[lbs]
–
[5 - 11.02] / [6.76 - 14.90]
Trip units for power distribution TMF
TMA
– –
Ekip Dip
Ekip Touch
–
1 Current Limiting circuit breaker in 480V AC and 600V AC 2 2-poles version available only as complete circuit breaker with TMF; 4-poles version available only as complete circuit breaker from In=80 to In=250 with TMF 3 600Y/347
Made with FlippingBook Online newsletter creator