BuyLog Flippingbook FEB 2025
6-11
MOLDED CASE CIRCUIT BREAKERS, BUYLOG SECTION 6
— Tmax XT circuit breakers for (AC) distribution
Molded case circuit breakers (MCCB)
XT1 125 3, 4
XT2 125 3, 4 600
Frame Size
[A]
Poles
[No.]
Rated voltage
(AC) 50-60Hz
[V]
480 V Δ 2
Versions
Fixed, Plug-in
Fixed, Plug-in, Withdrawable
L 1
V 1
X
Interrupting ratings
N
S
H
N S H 1
240 V (AC) 480 V (AC)
[kA] [kA]
50 25 18
65 35 22
100
65 100 150 200 200 200 25 35 65 100 150 200
65 25
600Y/347 V (AC) [kA]
–
–
–
–
–
–
600 V (AC)
[kA]
–
–
–
18 22 25 35 42 42
[No. Operations]
25000
25000
Mechanical life
[No. Hourly operations]
240
240
3-poles 4-poles
[mm]/[in] [mm]/[in] [kg]/[lbs]
[76.2 x 70 x 130] / [3 x 2.75 x 5.12]
[90 x 82.5 x 130] / [3.54 x 3.25 x 5.12]
Dimensions - Fixed (Width x Depth x Height)
[101.6 x 70 x 130] / [4 x 2.75 x 5.12] [120 x 82.5 x 130] / [4.72 x 3.25 x 5.12]
Fixed 3/4-poles
[1.1 - 2.43] / [1.4 - 3.07]
[1.2 - 2.65] / [1.6 - 3.53]
Plug-in (EF) 3/4-poles
[kg]/[lbs]
[2.21 - 4.87] / [2.82 - 6.22]
[2.54 - 5.60] / [3.27 - 7.21]
Weight
Withdrawable (EF) 3/4-poles
[kg]/[lbs]
–
[3.32 - 7.32] / [4.04 - 8.91]
Trip units for power distribution TMF
TMA
– –
Ekip Dip
Ekip Touch
–
1 Current Limiting circuit breaker in 480V AC and 600V AC 2 600Y/347
Made with FlippingBook Online newsletter creator