BuyLog Flippingbook NOV 2024

LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8

8-98

— EntelliGuard ™ G low voltage power circuit breakers EntelliGuard ™ G accessories

A wide range of optional accessories are interchangeable across all EntelliGuard G power circuit breakers, regardless of nominal rating or envelope/frame size.

Motorized Spring Charging Unit The unique motor/gearbox unit is specially designed to operate with the full range of EntelliGuard G breakers. It is easily installed with three heavy-duty bolts. After a breaker close operation, the unit automatically recharges the spring and makes it ready for immediate re close should the need arise. High speed recharging ensures that the springs are fully charged within approximately three seconds following a release. All electrically operated (EO) ANSI/UL breakers are equipped with “Spring Charged” contacts for status indication.

Motorized Spring Charging Unit

Power Consumption

Nominal Control Voltage 24Vdc/30Vdc

UL and IEC Range (85% to 110%) 20.4V to 26.4V 40.8V to 52.87V

Envelope

ANSI Range

Product Number

GM01024DR GM01048DR GM01060DR GM01072DR

48Vdc 60Vdc 72Vdc

38V to 56V

51V to 66V

– –

1

DC - 300W

61.2V to 79.2V

110Vdc/130Vdc

106.25V to 137.5V 100V to 140V GM01110DR

250Vdc 48Vac 120Vac 240Vac 277Vac

212.5V to 275V 40.8V to 52.87V 102V to 132V 204V to 264V 235.5V to 304.7V 20.4V to 26.4V 40.8V to 52.87V

200V to 280V GM01250DR

GM01048AR

104V to 127V GM01120AR 208V to 254V GM01240AR

1

AC - 350VA

Motorized Spring Charging Unit

– –

GM01277AR GM02024DR GM02048DR GM02060DR GM02060DR

24Vdc/30Vdc

48Vdc 60Vdc 72Vdc

38V to 56V

51V to 66V

– –

2 and 3

DC - 480W

61.2V to 79.2V

110Vdc/130Vdc

106.25V to 137.5V 100V to 140V GM02110DR

250Vdc 48Vac 120Vac 240Vac 277Vac

212.5V to 275V 40.8V to 52.87V 102V to 132V 204V to 264V 235.5V to 304.7V

200V to 280V GM02250DR

GM02048AR

104V to 127V GM02120AR 208V to 254V GM02240AR

2 and 3

AC - 560VA

GM02277AR

Made with FlippingBook - Online Brochure Maker