BuyLog Flippingbook NOV 2024
LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
8-98
— EntelliGuard ™ G low voltage power circuit breakers EntelliGuard ™ G accessories
A wide range of optional accessories are interchangeable across all EntelliGuard G power circuit breakers, regardless of nominal rating or envelope/frame size.
Motorized Spring Charging Unit The unique motor/gearbox unit is specially designed to operate with the full range of EntelliGuard G breakers. It is easily installed with three heavy-duty bolts. After a breaker close operation, the unit automatically recharges the spring and makes it ready for immediate re close should the need arise. High speed recharging ensures that the springs are fully charged within approximately three seconds following a release. All electrically operated (EO) ANSI/UL breakers are equipped with “Spring Charged” contacts for status indication.
Motorized Spring Charging Unit
Power Consumption
Nominal Control Voltage 24Vdc/30Vdc
UL and IEC Range (85% to 110%) 20.4V to 26.4V 40.8V to 52.87V
Envelope
ANSI Range
Product Number
–
GM01024DR GM01048DR GM01060DR GM01072DR
48Vdc 60Vdc 72Vdc
38V to 56V
51V to 66V
– –
1
DC - 300W
61.2V to 79.2V
110Vdc/130Vdc
106.25V to 137.5V 100V to 140V GM01110DR
250Vdc 48Vac 120Vac 240Vac 277Vac
212.5V to 275V 40.8V to 52.87V 102V to 132V 204V to 264V 235.5V to 304.7V 20.4V to 26.4V 40.8V to 52.87V
200V to 280V GM01250DR
–
GM01048AR
104V to 127V GM01120AR 208V to 254V GM01240AR
1
AC - 350VA
Motorized Spring Charging Unit
– –
GM01277AR GM02024DR GM02048DR GM02060DR GM02060DR
24Vdc/30Vdc
48Vdc 60Vdc 72Vdc
38V to 56V
51V to 66V
– –
2 and 3
DC - 480W
61.2V to 79.2V
110Vdc/130Vdc
106.25V to 137.5V 100V to 140V GM02110DR
250Vdc 48Vac 120Vac 240Vac 277Vac
212.5V to 275V 40.8V to 52.87V 102V to 132V 204V to 264V 235.5V to 304.7V
200V to 280V GM02250DR
–
GM02048AR
104V to 127V GM02120AR 208V to 254V GM02240AR
2 and 3
AC - 560VA
–
GM02277AR
Made with FlippingBook - Online Brochure Maker