SURGE PROTECTION DEVICES, BUYLOG SECTION 20
20-6
— ReliaGear Surge Protective Device RGMESP
ReliaGear® RGMESP Series SPDs are engineered with smart thermal disconnecting technology that safely removes overstressed components before harmful external effects arise. This preventive approach enhances safety and avoids nuisance from OCPD tripping or thermal events. The core suppression system includes proprietary Metal Oxide Varistors (MOVs) for surge energy diversion and metal film capacitors for filtering low-level transient voltages and electrical noise. The design is UL Listed, suitable for all NEC compliant installations.
Standards: • UL 1449 5th Ed. – Listed, —Mil-Std-220C
• UL 1283 Listed EMI/RFI Filter—ANSI/NFPA 70 (Art. 242) • UL 96A – Meets SPD criteria—ANSI/IEEE C62.41 & .45 • cUL Listed to UL 1449 & CSA C22.2—ANSI/IEEE C62.62 & .7 • IEC 61643-11
Voltage Part number 120S 240 / 120 1-phase, 3-wire + ground RGMESP120S XX T2 120Y 208Y / 120 3-phase, 4-wire + ground RGMESP120Y XX T2 240D 240 Delta 3-phase, 3-wire + ground RGMESP240D XX T2 240H 240 / 120 Hi-Leg Delta 3-phase, 4-wire + ground RGMESP240H XX T2 220Y 380Y / 220 3-phase, 4-wire + ground RGMESP220Y XX T2 240Y 415Y / 240 3-phase, 4-wire + ground RGMESP240Y XX T2 277Y 480Y / 277 3-phase, 4-wire + ground RGMESP277Y XX T2 480D 480 Delta 3-phase, 3-wire + ground RGMESP480D XX T2 Desired kA XX Code 80 kA/mode 08 100kA/mode 10 Configuration
Electrical characteristics Maximum surge current rating Nominal discharge current rating (In)
80 kA per mode / 160 kA per phase 100 kA per mode / 200 kA per phase
20 kA
Operating frequency 50–60 Hz Surge life (IEEE C62.41 - C3 10 kA ) ≥5,000 impulses Modes of protection
All modes (L-N, L-G, N-G, L-L)
Fault rating (SCCR)
200 kA for all models Status indicator lights (one per phase) Standard dry (form C)
Standard monitoring
relay contacts Audible alarm
EMI / RFI filter attenuation Maximum attenuation frequency -61 dB at 100.2 kHz Mechanical characteristics Weight 5.1lb (2.3 kg) Enclosure type
Polymer, UL 94 5VA polycarbonate, black. NEMA 4/ Type 4 Service entrance equipment, primary distribution equipment – Rated for UL and NEC Type 2 installation locations
Installation location
Dual mounting flanges / 3 ⁄ 4 " NPT offset nipple
Mounting method
Operating temperature
-40 °F to 149 °F (-40 °C to 65 °C)
Altitude
< 13,000 ft (3.96 km) Thermal fuse technology
Product design
Regulations and certifications UL 1449 5th edition
Type 2 Type 2 Type 2
cUL, CSA C22.2
UL 1283 UL 96A
Yes Yes
IEEE C62.62, C62.72
Listed by
UL