LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
— SACE Emax 3 low voltage power circuit breakers UL 1066
Common data Rated maximum voltage
[V] [V]
635 600
Rated voltage
Test voltage (1min. 50/60 Hz)
[kV] [Hz]
2.2
Frequency
50 - 60
Number of poles
3-4
Version
Fixed (F) - Drawout (W)
SACE Emax 3 UL 1066 Performance levels
E6.3 H-A 4000 5000
V-A
Rated uninterrupted current Iu @ 40°C
[A] [A] [A]
4000 5000
6000 1 50-100
6000 1 50-100
Neutral pole current-carrying capacity for 4-pole CBs Interrupting rating at rated maximum voltage
[%Iu]
254 V 508 V 635 V
[kA] [kA] [kA] [kA]
85 85 85 85 40 25
100 100 100 100
Rated short time current (30 cycle/0.5s)
Breaking 2
Breaking time for l
40 25
1 3 poles and draw out only - Overall dimension as 4 poles full size 2 Total clearing time is the sum of breaking time and trip time
Dimensions and weight Dimensions
H - Fixed/Drawout D - Fixed/Drawout
[in/mm] [in/mm]
14.61 [in] - 371 [mm]/16.73 [in]- 425 [mm] 10.63 [in]- 270 [mm]/ 15.47 [in]-393 [mm] 30 [in]-762[mm]/34.96 [in] - 888 [mm]/39.92 [in] - 1014 [mm] 31.61 [in] - 803[mm]/36.57 [in] - 929 [mm]/ 42.09 [in] - 1069 [mm]
W - Fixed 3p/4p/4p full size
[in/mm]
W - Drawout 3p/4p/4p full size
[in/mm]
Weights (CB with trip unit/current sensors/standard accessories)
Fixed 3p/4p/4p full size
[lbs/Kg]
314 [lbs]- 142 [kg]/360 [lbs]-163 [kg]/ 406 [lbs] - 184 [kg] Up to 5000A: 486 [lbs]-220 [kg]/ 554 [lbs]-251 [kg]/620 [lbs] -281 [kg] 6000A: 818 [lbs] - 371 [kg]
Drawout 3p/4p/4p full size including fixed part
[lbs/Kg]
SACE Emax 3 UL 1066
E6.3 4000
Mechanical life with regular ordinary maintenance prescribed by the manufacturer [Iu]
[A]
5000
6000
[No. cycles x 1000]
12 60
12 60
12 60
Frequency
[Oper./Hour]
Electrical life with regular ordinary maintenance prescribed by the manufacturer
508 V 635 V
[No. cycles x 1000] [No. cycles x 1000]
4 4
3 2
2 2
Frequency
[Oper./Hour]
10
10
10