LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
8-6
— SACE Emax 3 low voltage power circuit breakers UL 1066
Common data Rated maximum voltage
[V] [V]
635 600
Rated voltage
Test voltage (1min. 50/60 Hz)
[kV] [Hz]
2.2
Frequency
50 - 60
Number of poles
3-4
Version
Fixed (F) - Drawout (W)
SACE Emax 3 UL 1066 Performance levels
E4.3
S-A
H-A
V-A 800
Rated uninterrupted current Iu @ 40°C
[A] [A] [A] [A] [A] [A] [A]
2500 3000 3200
2500 3000 3200
1600 2000 2500 3000 3200
Neutral pole current-carrying capacity for 4-pole CBs Interrupting rating at rated maximum voltage
[%Iu]
100
100
100 100 100 100 100
254 V 508 V 635 V
[kA] [kA] [kA] [kA]
65 65 65 65 40 25
85 85 85 85 40 25
Rated short time current (30 cycle/0.5s)
Breaking (1)
Breaking time for l
40 25
1 Total clearing time is the sum of breaking time and trip time
Dimensions and weight Dimensions
H - Fixed/Drawout D - Fixed/Drawout W - Fixed 3p/4p W - Drawout 3p/4p
[in/mm] [in/mm] [in/mm] [in/mm]
14.61 [in] - 371 [mm]/16.73 [in]- 425 [mm] 10.63 [in]- 270 [mm]/ 15.47 [in]-393 [mm] 15.12[in] - 384 [mm]/20.08 [in]-510 [mm] 16.73 [in] - 425/[mm]/21.69 [in] -551 [mm] Up to 2500A: 161[lbs] - 73 [kg]/203 [lbs] - 92 [kg]; 3200A: 201[lbs]-91 [kg]/256 [lbs] -116 [kg] ; 3600A: 210 [lbs] - 95 [kg] Up to 2500A: 261 [lbs]-118 [kg]/325 [lbs] - 147 [kg]; 3200A: 300 [lbs]- 136 [kg]/377 [lbs] - 171 [kg]
Weights (CB with trip unit/current sensors/standard accessories)
Fixed 3p/4p
[lbs/Kg]
Drawout 3p/4p including fixed part
[lbs/Kg]
SACE Emax 3 UL 1066
E4.3
Mechanical life with regular ordinary maintenance prescribed by the manufacturer [Iu]
[A]
< 800
800
1200
[No. cycles x 1000]
20 60
20 60
20 60
Frequency
[Oper./Hour]
Electrical life with regular ordinary maintenance prescribed by the manufacturer
508 V 635 V
[No. cycles x 1000] [No. cycles x 1000]
8 8
8 8
7
6,5
Frequency
[Oper./Hour]
30
30
30