BuyLog Flippingbook MAY 2025
DISCONNECT SWITCHES AND OPERATING MECHANISMS, BUYLOG SECTION 9
9-154
— OTDC S1.0-Series IEC and UL Technical data
Technical data according to IEC 60947 for switch-disconnectors OTDC100…250E_
Switch size
OTDC100E OTDC160E OTDC200E OTDC250E
Rated insulation voltage Ui
Pollution degree 3
V 1500
1500
1500
1500
Rated impulse withstand voltage
kV 12
12
12
12
In open air, normal conditions 1
A A A A
100
160 154 142 128 160 160 160 70
200 193 177 160 200 200 200 95
250 241 222 200 120 250 250
In enclosure 40°C In enclosure 50°C In enclosure 60°C
96 89 80
Rated thermal current Ith 2
OTDC100...250E/U_
...with cable or bar cross section Cu
mm² 35
1 circuit 2P (1P+, 1P-) A 2 circuits 4P (2P+, 2P-) A 3 circuits 6P (3P+, 3P-) A
100 100 100
Rated operational current DC-21B, poles in series
1000 V
1s
kA kA
5
5
5
5
Rated short-time withstand current, 1000 V
R.M.S. - value Icw
0.1s
10
10
10
10
Power loss / pole Terminal bolt size
At rated current
W
2
4
6
9,5
Metric thread diameter x length mm
M8x25 M8x25 M8x25 M8x25 15…22 15…22 15…22 15…22
Terminal tightening torque
Counter torque required
Nm
1 Normal conditions defined in IEC 60947-1, section 6.1 2 Ambient max. average 24h
Technical data in accordance to UL98B for photovoltaic disconnect switches OTDC100…200U_ Suitable for use in photovoltaic systems in accordance with Article 690 of the NEC.
Switch size
OTDC100U
OTDC200U
UL Listed
Standard
UL98B
UL98B
Rated ambient temperature
°C
-20…+50
-20…+50
1 circuit
2P (1P+, 1P-)
A A A
100 100 100
200 200 200
Rated current
1000 V
2 circuits 4P (2P+, 2P-) 3 circuits 6P (3P+, 3P-)
kA
10
10
Short circuit rating Protection type
1000 V
Circuit breaker
Circuit breaker
Mechanical lug
OZXA200
OZXA200
Wire range
Cu/Al
AWG 4-300MCM AWG 4-300MCM
Tightening torque
lb-in. 200
200
Technical data according to IEC 60947
See IEC table for type
OTDC160E
OTDC250E
Made with FlippingBook - professional solution for displaying marketing and sales documents online