BuyLog Flippingbook MAY 2025
DISCONNECT SWITCHES AND OPERATING MECHANISMS, BUYLOG SECTION 9
9-150
— OTDC XS-Series IEC and UL Technical data
— Technical data according to IEC 60947 for switch-disconnectors OTDC16…32U_
Switch size
OTDC16U
OTDC25U
OTDC32U
Pollution degree 2 1 Pollution degree 3 1
V 1250 V 1000
1250 1000
1250 1000
Rated insulation voltage Ui
Rated impulse withstand voltage
kV 8
8
8
In open air, normal conditions 2 In enclosure 40°C In enclosure 60°C
A
40
50
63
OTDC16...32U_
Rated thermal current Ith
A A
32 25
40 32
50 40 10
...with cable or bar cross section
Cu
mm² 4
6
One circuit
V 16/2P
25/2P
32/2P
660 V
Two circuits
V 16/2Px2
25/2Px2 25/2Px3
32/2Px2 32/2Px3
Three circuits V 16/2Px3
Rated operational current DC-21B / Poles in series
One circuit
V 10/2P
16/2P
20/2P
Two circuits
V 10/2Px2
16/2Px2 16/2Px3
20/2Px2 20/2Px3
1000 V 3
Three circuits V 10/2Px3
Rated short-time withstand current, 1000 V, 1 s Rated conditional short-circuit current I p (r.m.s.)
R.M.S. -value I cw
kA
1,0
1,0
1,0
I p (r.m.s.), 1000 V Max fuse size, gPV
kA
10 80
10 80
10 80
A
At rated current
Power loss / pole
W
0,1
0,2
0,35
Terminal cable size
Cu
mm² 2.5…16
2.5…16 1.2...1.4
2.5…16 1.2...1.4
Terminal tightening torque
Counter torque required Nm
1.2...1.4
1 When used with external handle. For use with direct mounted handle, see installation instruction. 2 Normal conditions defined in IEC 60947-1, section 6.1. 3 U and UT types only. (Not applicable for US nor UST)
— Technical data in accordance to UL508I for photovoltaic disconnect switches OTDC16…32U_ Suitable for use in photovoltaic systems in accordance with article 690 of the NEC.
Switch size
OTDC16U
OTDC25U
OTDC32U
UL Listed
Standard
UL508i
UL508i
UL508i
Rated ambient temperature
°C
-20…+60
-20…+60
-20…+60
One circuit
A
16/2P
25/2P
Rated current / Poles in series
600 V
Two circuits A Three circuits A
16/2Px2 16/2Px3
25/2Px2
32/2Px2
Short circuit rating
600 V
kA
5
5
5
Protection type
Max fuse size, RK5 fuse
A
80
80
80
Wire range
AWG 12-6
AWG 12-6
AWG 12-6
Technical data according to IEC 60947
See IEC table for type
OTDC16U
OTDC25U
OTDC32U
Made with FlippingBook - professional solution for displaying marketing and sales documents online