— Accessories for fusible disconnect switches OS Mini 30A Technical information for auxiliary contacts
ON
Handle indications and functions
The handle indicates the position of the contacts with complete reliability in all situations. If the contacts are welded together, the handle doesn't reach the OFF-position but remains between ON and OFF, maintaining the door interlock and padlocking is not possible to do. When operating the switch fuse to the Test-position with a test handle the test auxiliary contacts change position. The main contacts remain open.
OFF
Test
ON and OFF-functions of main and auxiliary contacts
-45 ˚
0 ˚
30 ˚
60 ˚
90 ˚
Example
α
close
Main contacts NO auxiliary contact NC auxiliary contact
open
Places of auxiliary contacts and Test ind.
2
close open
1
open
close
1
close open
NO auxiliary contact NC auxiliary contact
2
open
close
Test
OFF O
ON I
OS Mini
-45 ˚
0 ˚
30 ˚
60 ˚
90 ˚
α
Main contacts NO auxiliary contact NC auxiliary contact
OA4B1C, 1 NO-NC
Change over contacts
OA1G10, 1NO OA3G01, 1NC
NO auxiliary contact NC auxiliary contact
Test
OFF O
ON I
0˚
30 ˚
60 ˚
90 ˚
α
O O
I I
Main contacts
NO auxiliary contact
MCB-10 + OESA-ZX169, 1NO MCB-01 + OESA-ZX169, 1NC
NC auxiliary contact
OFF O
ON I
OS30...63
-45 ˚
0 ˚
30 ˚
60 ˚
90 ˚
α