BuyLog Flippingbook FEB 2025
LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
8-146
— Gerapid high speed DC circuit breakers
Technical Data for Feeder Circuit Breaker Models 2607 through 8007
Gerapid 8007
Breaker type
Gerapid 2607
Gerapid 4207
Gerapid 6007
Arc chute type
1X2 1X4 2X2 2X3 2X4 1X2 1X4 2X2 2X3 2X4 1X2 1X4 2X2 2X3 2X4 1X2 2X2
Conventional thermal current Ith [A]
(IEC/EN)
2600
4200
6000
8000
Rated current [A]
(ANSI/IEEE C37.14)
2600
4150
N/A
6000
Rated voltage U Ne [V]
EN 50123 / IEC 60947) 1000 2000 2000 3000 3600 1000 2000 2000 3000 3600 1000 2000 2000 3000 3600 1000 2000
Rated maximum voltage [V] N/A Rated insulation voltage U i [V] EN 50123 / IEC 60947) 2000 2000 2000 3000 4000 2000 2000 2000 3000 4000 1000 2000 2000 3000 4000 1000 2000 Short time current 120 min [A] EN 50123 / IEC 60947) 3150 5000 7200 9600 Short time current 2 min [A] EN 50123 / IEC 60947) 5200 8500 12000 16000 Short time current 20 sec [A] EN 50123 / IEC 60947) 7800 12600 18000 24000 Impulse withstand voltage 1.2/50 μs U i [kV] according to EN 50124-1:1997 18 18 18 30 30 18 18 18 30 30 12 18 18 30 * 12 18 Power frequency withstand voltage 50 Hz U a [kVeff] according to EN 50124-1:1997 101010151510101015157 101015 * 7 10 Rated short circuit making capacity ÎN ss [kA] 70 50 100 50 42 70 50 100 50 42 70 50 80 50 * 70 * Rated short circuit breaking capacity according to EN 50123-2 IN ss [kA] 50 35 71 35 30 50 35 71 35 30 50 35 56 35 * 50 50 Rated service short circuit breaking current according to IEC 947-2 Ics [kA] 60 40 50 40 40 60 40 50 40 40 60 40 50 40 * 60 * Short circuit current according to IEEE C37.14 [kA] 120 – – – – 120 – 60 – – – – – – – 120 * Peak current according to IEEE C37.14 [kA] 200 – – – – 200 – 100 – – – – – – – 200 * Maximum short circuit current [kA] tested at customer request 244 120 100 – 52 244 120 100 – 52 200 – – – – 240 – Maximum arc voltage Uarc [kV] (EN 50123 / IEC 60947) 2445.672445.672445.6724 Weight ca. [kg] 120 120 160 160 160 120 120 160 160 160 150 150 165 165 165 190 210 Weight ca. [lbs] 265 265 352 352 352 265 265 352 352 352 331 331 364 364 364 419 463 *Test data available at customer request (ANSI/IEEE C37.14) 800 N/A N/A N/A N/A 800 N/A 1600 N/A N/A N/A N/A N/A N/A N/A 800
Technical Data for Rectifier Circuit Breaker Models 8007R and 10007R Parameter Reference Gerapid 8007R
Gerapid 10007R
Arc chute type
N/A
1x2
1x3
1x2
1x3
Rated continuous current [A]
ANSI C37.14 p.5.3
6000 7200
6000 7200
8000 9600
8000 9600
2 hours current [A] 2 minutes current [A] 20 seconds current [A]
N/A N/A N/A
12000 18000
12000 18000
16000 24000
16000 24000
Rated short-time current (250ms) [kA] Rated maximum voltage [V] Rated insulation voltage - U Nm [V] Rated impulse voltage - U Ni [kV] Power frequency voltage – U a [kV] Mechanical endurance [cycles] 1 Rated short circuit peak / sustained current [kA] 2,3
ANSI C37.14 p.5.5 ANSI C37.14 p.5.2 EN 50124-1 p.1.3.2.4 EN 50124-1 p.1.3.2.7 EN 50124-1 a.B 2.2
90 (149 peak)
60 (100 peak)
90 (149 peak)
60 (100 peak)
800
1200 2000
800
1200 2000
2000
2000
18 [12/50 μs]
18 [12/50 μs]
18 [12/50 μs]
18 [12/50 μs]
10 [1 minute 50 Hz] 10 [1 minute 50 Hz] 10 [1 minute 50 Hz] 10 [1 minute 50 Hz]
N/A
10.000
10000
10000
10000
ANSI C37.14 p.5.4
200 / 120
132 / 80
200 / 120
132 / 80
Short-circuit characteristic Maximum arc voltage [V]
Tests a, b, c, d acc. ANSI C37.14 annex A
High-speed
High-speed
High-speed
High-speed
N/A N/A
2500
2500
2500
2500
Mass ca.
220 kG
220 kG
220 kG
220 kG
1 10000 cycles without parts replacement. Inspection after 5000 cycles. Max. 5000 cycles by means of ED impulse coil or POCT release. 2 Tested for high and low frequency impedance bonds. 3 Trip by means of POCT (direct-acting, instantaneous, electromechanical and polarized OC release) or by means of ED impulse coil with no intentional delay
To configure Gerapid OEM Modules and DC Circuit Breakers, visit our web\ wizard configuration tool at: http://electrification.us.abb.com/cwc/Dispatcher?REQUEST=PRODUCTS&id=gerapid&lang=en_US
Made with FlippingBook Online newsletter creator