BuyLog Flippingbook FEB 2025

6-163

MOLDED CASE CIRCUIT BREAKERS, BUYLOG SECTION 6

— Record Plus ™ FB 100

Reference Publications Available for download from electrification.us.abb.com/publibrary FB Breaker Installation Instructions Fact sheet DEH-41073 DET-406 FB Breaker Accessories Bell Alarm & Aux. Switch Shunt Trip & UVR Padlock Device Lug Kits DEH-40324 DEH-40363 DEH-40521 DEH-40532

Breaker Frame Rating Product Description Standards & Ratings Interrupting Ratings Lug Data & Torque Info Product Number Push to Trip

Panelboards A-Series ™ AD Plus Catalog/Selection Guide A-Series ™ AD Plus Fact Sheet

DEP-134 DET-397

Spectra ™ Power Panel - Plug-in Kits Spectra ™ Power Panel - Bolt-on Kits Spectra ™ Power Panel - Filler Plates

DEH-41123 DEH-41124 DEH-41125

Outline Drawings FB 1 pole FB 2 pole FB 3 pole

10091632SH1 10091636SH1 10091641SH1

Series Ratings

DET-008

FB Breaker Markings cULus

Trip Curves Trip Unit Rated Current (A)

UL File E-11592

Trip Curve DES-013 DES-014 DES-015 DES-016 DES-017 DES-018 DES-019 DES-020 DES-021 DES-022 DES-023 DES-024 DES-025 DES-030 DES-031

15 20 25 30 35 40 45 50 60 70 80 90

HACR

15 to 100A 15 to 50A 15 to 100A 15 to 100A 15 to 100A

1, 2, 3 Pole 1, 2, 3 Pole 1, 2, 3 Pole 1, 2, 3 Pole 1, 2, 3 Pole

HID

NAVAL

Cu/Al 60/75°C Current Limiting

FB breakers are NOT marked LINE/LOAD and can be reverse fed.

100

Peak Current Curves

Peak I²t Curve

FB Breaker Markings

UL Listed Interrupting Ratings - rms Symmetrical Amperes (in Thousands) AC Voltage

Type

Ampere Rating Max AC Voltage No. Poles

240

277

347

480

600/347

1 2 3 1 2 3 1 2 3 1 2 3

35 65 65 65

35

22

FBV

15-100

600/347VAC

– – – – – – – –

– – – – – – – –

35 35 65 65 –

22 22 25 25 35 35 42 42 – – –

65

25

FBN

15-100

600/347VAC

150 150 100 200 200 100 200 200

100

35

FBH

15-100

600/347VAC

100 100 150 150 –

150

42

FBL

15-100

600/347VAC

FB breakers are NOT marked LINE/LOAD and can be reverse fed.

Product Number Structure

3 6 TE 050 R

F B N

Family F = Family Record Plus Frame Rating (Amperes) B = 100 Interruption Rating (480V) V = 35kA N = 65kA

Connection R = Standard, No Lugs R2 = Load Lugs Only RV = A-Series ™ AD Plus Lighting

Panel (Includes Load Lugs and panel connections)

H = 100kA L = 150kA

Rated Current (A) 1 015-100

Type TE = Fixed Thermal Magnetic

Poles 1 = 1 pole

2 = 2 poles

3 = 3-poles

Voltage Rating 6 = 600/347

1 Available ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100.

Made with FlippingBook Online newsletter creator