BuyLog Flippingbook FEB 2025
6-9
MOLDED CASE CIRCUIT BREAKERS, BUYLOG SECTION 6
— Formula circuit breakers for power distribution General characteristics
The FORMULA circuit breakers from 15 A to 250 A consist of the interruption component together with the trip unit and can be installed: • Directly on the back plate of cubicles • On a DIN rail
They are characterized by: • Fixed version • Polarity: 1-pole, 2-pole, 3-pole • Maximum breaking capacity of 25 kA at 240 V AC • Fixed thermal-magnetic trip unit (TMF) for protection of networks in alternating current • A single depth of 2.36" • Standard front terminals
FORMULA A1
FORMULA A2
— 1-pole
— 2-pole
— 2-pole
— 3-pole
A1
A2
Frame size
A A
100
250
Rated current, In
15–100
125–250
Poles
No.
1, 2, 3
2, 3
Rated service voltage, Ue (AC) 50–60 Hz (DC)
V
240 (1p, 2p, 3p) 125 (1p), 250 (2p,3p)
240 (2p, 3p) 250 (2p,3p)
Versions
Fixed
Fixed
Performance Level
A 1
N
A
N
Pole
No.
2, 3
1
2, 3
2, 3
2, 3
Rated ultimate short circuit breaking capacity, Icu Interrupting rating at 240 V 50–60 Hz (AC) Interrupting rating at 125 V (DC) 1-pole (in 2012) Interrupting rating at 250 V (DC) 2-pole in series (2p, 3p) (in 2012)
kA kA
10
10
18 10
25
10
25
5
–
–
–
–
kA –
5
–
10
10
25
Reference standard Isolation behavior Mounting onto DIN rail
UL 489
UL 489
Yes
Yes
DIN EN 50022
DIN EN 50022
Dimensions (width x depth x height) 1-pole
in. in. in.
1.00 x 2.36 x 5.12 2.00 x 2.36 x 5.12 3.00 x 2.36 x 5.12
–
2-pole 3-pole
2.76 x 2.36 x 5.91 4.13 x 2.36 x 5.91
Weight 1-pole
lbs. lbs. lbs.
0.54 1.04 1.54
–
2-pole 3-pole
1.61 2.43
Trip unit — Thermal-magnetic TMF
Yes
Yes
Made with FlippingBook Online newsletter creator