Control_Flippingbook_JULY 2026

NEMA FULL VOLTAGE POWER DEVICES, CONTROL SECTION 1

1-114

— Plug and play enclosed starters 3-phase starters, combination non-fusible disconnect switch 1

— HP rated, combination starters, non-fusible disconnect, non-reversing

Maximum motor HP ratings

Type 1

Type 4/12

Type 4X

Contactor size

200/ 208 V

220/ 240 V

460/ 480 V

575/ 600 V

Ordering code

Ordering code

Ordering code

Motor switching current 2

9

AF09 AF16 AF30 AF52 AF80

2 5

2 5

5

7.5 15 25 50 75

PS-AFSN13 PS-AFSN43 PS-0FSN13 PS-0FSN43 PS-1FSN13 PS-1FSN43 PS-2FSN13 PS-2FSN43 PS-3FSN13 PS-3FSN43 PS-4FSN13 PS-4FSN43

PS-AFSNX3 PS-0FSNX3 PS-1FSNX3 PS-2FSNX3 PS-3FSNX3 PS-4FSNX3

17 27 52 77

10 20 40 60

10 15 25 40

10 20 30 50

125

AF140

100

125

— NEMA, combination starters, non-fusible disconnect, non-reversing

Maximum motor HP ratings

Type 1

Type 4/12

Type 4X

HP rated

NEMA size

Contactor size

Continuous current

Ordering code

Ordering code

Ordering code

200 V 230 V 460/575 V

00

AF09 AF12 AF26 AF40 AF80

9

1.5

1.5

2 PSN-AFSN13 PSN-AFSN43 5 PSN-0FSN13 PSN-0FSN43 10 PSN-1FSN13 PSN-1FSN43 25 PSN-2FSN13 PSN-2FSN43 50 PSN-3FSN13 PSN-3FSN43 100 PSN-4FSN13 PSN-4FSN43

PSN-AFSNX3 PSN-0FSNX3 PSN-1FSNX3 PSN-2FSNX3 PSN-3FSNX3 PSN-4FSNX3

0 1 2 3 4

18 27 45 90

3

3

7.5 10 25 40

7.5 15 30 50

AF140

135

Coil voltage selection All AC-operated ordering codes include a 100–250 V AC coil. To select other coil voltages, substitute the code from the coil voltage selection chart for the last digit in the ordering code. Ex. : A 24–60 V AC coil is required for an AF09 contactor; use PS-AFSN11.

Volts

Hz

24-60

48-130

100-250

250-500

NEMA

50/60

1

2

3

4

¹Overload relays, pilot device kits and control transformers must be ordered separately (see pages 115–122). ²Ratings listed are at 600 V AC.

Made with FlippingBook - Share PDF online