BuyLog Flippingbook NOV 2024

LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8

8-90

— EntelliGuard ™ G circuit breaker EntelliGuard ™ G circuit breaker nomenclature

EntelliGuard ™ G Circuit Breaker Product Number Structure

GA16M1HERX5RAXXL4X6V Digit 1 2 3, 4 5 6 7 8 9 10 11 12 13 14 15 16, 17 18 19 20 Digit

Rating Plug 1900

Circuit Breaker Family G = EntelliGuard ™ G Breaker/Switch

Advanced Features and Communications Monitoring + Data acq., Modbus Protocol + RELT

Breaker Switch Type A = ANSI/U 1066 Circuit Breaker Current Rating/Sensors 16 = 1600A Short Circuit Withstand Rating Interrupting Rating Tier ANSI/UL 1066

Zone Selective Interlocking (ZSI) None

Overcurrent Protection Ground Fault LSIG

Mechanical Interlock None DEFAULT

Mounting M = OEM, Drawout, 3 poles

Spring Charge Motor 1 = AC - 120Vac

Key Interlock & Padlock Provisions None

Closing Devices E = Closing Coil - 110Vdc/130Vdc; 120Vac

Bell Alarm, Mechanical Counter, Trip Annunciation Bell Alarm Contact with lockout

Shunt Trip R = 110/125Vdc; 120Vac

Auxiliary Switch, Coil Signaling Contact CSC, Hi-Fi Via Trip Unit - 2nd ST or 2nd UVR

Under Voltage Release (UVR) X = None

Second Shunt Trip, Second UVR R = Second Extended Range Shunt Trip 110/125Vdc; 120Vac

Digit 1 Circuit Breaker Family Device Series Line EntelliGuard ™ G Breaker/Switch

Digits 3 and 4 Current Rating /Sensors Current Sensor Rating (A) Circuit Breaker ANSI UL489

Code

Switches 1

ANSI

UL489

G

400 600 800

04

04 06 08 10 12 16 20 25 30 40 50 60 –

– –

– –

08

08

08

Digit 2 Breaker Switch Type Breaker/Switch Type, Secondary Mounting

1000 1200 1600 2000 2500 3000 3200 4000 5000 6000

– –

– –

Envelope 1

Envelope 2 & 3

12 16 20 25 30

Side

Top

Top

16 20

16 20

ANSI/UL1066 Circuit Breaker

A B

N U

A B

UL 489 Circuit Breaker ANSI Non-auto CB (ANSI Switch) UL489 Non-auto CB UL Switch)

– –

– –

C

M

C

32 40 50

32 40 50

D

S

D

40 50

Top = Top Mounted Secondary Disconnects (TSD). Side = Side Mounted Secondary Disconnects (SSD). (Available on Envelope 1 only.) NOTE: N, U, M, S characters are for Envelope 1 only with top mounted secondary disconnects (TSD). When ordering codes A, B, C, D, Side Secondary Disconnects (SSD) are supplied as standard on Envelope 1. Codes N, U, M, S are not valid for Envelopes 2 and 3. Envelope 1 (Type N and H, 400A - 2000A). NOTE: DC Ratings; trip unit not included. DC Rated Circuit Breakers require external control devices (e.g., Type 37 or Type 76 DC Relays). NOTE: Side Secondary Disconnects are specifically intended for 5-High ("high density") equipment designs. With Side Mounted Disconnects (SSD), the following Aux. Switches are not valid (In Digit 12); Auxiliary Switch, 8NO+8NC (Power Rated) or Aux. Switch, 4NO/4NC (Power Rated) + 4NO/4NC (High Fidelity).

– 60 1 Switches (Digit 2 = M, S, C, D) do not have current Sensors or a trip unit –

Made with FlippingBook - Online Brochure Maker