BuyLog Flippingbook MAR 2024
19-5
PDU AND STS, BUYLOG SECTION 19
— TruFit PDU Power Distribution Unit (PDU) Overview
42"
60"
Technical specifications TruFit Series
50-300 kVA
400-800 kVA
General data Standards
ETL listed to UL 891
Access requirements
Front only for installation, operation, and maintenance
Cable entry/exit
Top and/or bottom
Mechanical characteristics Main cabinet Dimensions
42"W x 36"D x 78"H
60"W x 48"D x 84"H
Weight
= 2650 lbs
= 5500 lbs
Front-facing sidecar(s) Dimensions
24"W x 36"D x 78"H
30"W x 48"D x 84"H
Weight
= 340 lbs
= 550 lbs
Transformer kVA rating
50, 75, 125, 150, 225, 300
400, 500, 600, 750, 800
Input/primary voltage
480 VAC, 3-phase, 3-wire + ground
480 VAC, 3-phase, 3-wire + ground Re-tappable dual output 415/240 VAC & 208/120 VAC
Output/secondary voltage
208/120 VAC, 3-phase, 4-wire + ground
Single output 415/240 VAC Single output 208/120 VAC Aluminum (std.), Copper (opt.)
Winding material
Aluminum (std.), Copper (opt.)
Output/distribution specifications Panelboard distribution Panelboard types/brand
ABB XT3, ABB XT4, ABB XT5
ABB XT4, ABB XT5, ABB XT6 250A, 400A, 600A, 800A
Panelboard amp rating Sub-feed circuit breakers Sub-feed types/brand
225A, 250A, 400A
ABB XT3, ABB XT4, ABB XT5
ABB XT4, ABB XT5, ABB XT6 250A, 400A, 600A, 800A
Sub-feed amp rating
225A, 250A, 400A
Made with FlippingBook Ebook Creator