BuyLog Flippingbook MAR 2024
POWER CONDITIONING, BUYLOG SECTION 18
18-8
— PCS100 AVC-40 Technical specification
Utility – Input Power range
150 – 3600 kVA
Voltage (model specific) Nominal supply frequency
220 V – 480 V, 3-phase
50 Hz or 60 Hz
Load - Output Voltage
To match nominal input voltage
Displacement power factor
0 lagging to 0.9 leading
Efficiency
Typically >98%
Initial < 250 µs, complete < ½ cycle
Sag correction response
±1% typical, ±2% maximum
Voltage regulation accuracy
Sag correction accuracy Continuous regulation range Sag correction capability
±4%
±10%
40%
Overload capability
150% for 30 seconds, once every 500 seconds 125% for 10 minutes, 150% for 1 minute, 500% for 1 second, 2000% for 200 ms
Bypass overload capacity
Environmental Operating temperature range
0° C to 50° C 32° F to 122° F <75 dBA @ 2m
Noise
Enclosure rating
IP20
User interface User interface
10.1” color touch panel, multilingual
Touch panel
Full parameter control, system event log, voltage event log
Communication
Ethernet, Modbus TCP, E-mail
Standards and certifications Quality
ISO 9001 ISO 14001 CE, C-Tick IEC 62103
Environmental
Marking
Safety
Emissions: CISPR 11 Class A Group 1 Immunity: IEC 61000-6-2
Electromagnetic compatibility
Performance
IEC 61000-4-34
Made with FlippingBook Ebook Creator