17-5
UPS, BUYLOG SECTION 17
— UPS high power MegaFlex UL UPS Technical specifications
General data
415V
480V
System power rating [kW] Core power rating [kW]
1,000 / 1,100 / 1,200 / 1,250 / 1,350
1,000 / 1,100 / 1,200 / 1,500 / 1,600
337
400
Topology
Online double conversion
Parallel system capacity
Up to 4 UPS systems via RPA Decentralized Architecture Up to 25% more flexibility on cable length in case of RPA system.
Static Bypass Inductor (Standard)
Cable entry Serviceability
Top or bottom
Front and top service access
HRG Ready
Yes
Input Connections
Single or Dual Feed
Short Circuit Withstand Rating
100 kAIC
Static Bypass Cabinet color
100% Rated – Continuous Duty
RAL 9005 (black)
Input Nominal input voltage
415 VAC, 3-ph, 4 W + ground
480 VAC, 3-ph, 3 W + ground
Voltage tolerance
-15% to +15%
Current distortion THDi
<3.0% 100% load normal mode – linear
Frequency range
60 Hz +/-10%
Power factor
0.99
Output Rated output voltage
415 VAC ph-ph, 240 VAC ph-n
480 VAC ph-ph
Static: +/-1% Dynamic (step load 0%-100%-0) Dynamic (step load 0%-50%-0)
Voltage tolerance
+/-3 +/-2
<3 @ 100% load-normal mode – linear <5 @ 100% load-normal mode – non-linear
Voltage distortion THDu
Frequency
60 Hz
Rated power factor
1.0
Efficiency Double conversion (VFI) eBoost Mode (VFD) Environment Protection rating Storage temperature Operating temperature Altitude without de-rating
Up to 97% Up to 99%
IP20
-13 to 131°F / -25 to 55°C 32 to 104°F / 0 to 40°C
Up to 1,000 m
1,500 m: -2.5% / 2,500 m: -2.5% 1,500 m: -2.5% / 1,500 m: -2.5%
Altitude with de-rating
Acoustic noise at 1 m
<80 dBA
Communications User interface
System graphical touch screen
Communication ports Customer interface
RS232, SNMP & Modbus
Remote shutdown, gen-set interface, external bypass contact
Batteries Types
Lithium ion, VRLA, Pure Lead, NiCd & Ni-Zn
Nominal Battery Bus
480V (240 Cell)
Standards Safety
ETL as tested to UL1778 / EN 62040-1 / UL9540
EMC
C3
Manufacturing
ISO 9001:2015, ISO 14001:2015, OHSAS18001
Weight, dimensions
415V systems
480V systems
1,000 kW 8,157 lbs / 3,700 kgs
1,000, 1,100 & 1,200 kW 8,157 lbs / 3,700 kgs 1,500 & 1,600 kW 9,039 lbs / 4,900 kgs
Weight [lbs] [kg]
1,100, 1,200, 1,250 & 1,350 kW 9,039 lbs / 4,900 kgs
Dimensions w x h x d (in) (mm) 129.92 x 86.61 x 39.37 (in) 3,300 x 2,200 x 1,000 (mm) Changes to the product or to the information contained in this brochure are reserved; so are errors and omissions. Please reference ABB order confirmations and submittal documentation packages for job specific configurations.