BuyLog Flippingbook JAN 2026

17-5

UPS, BUYLOG SECTION 17

— UPS high power MegaFlex UL UPS Technical specifications

General data

415V

480V

System power rating [kW] Core power rating [kW]

1,000 / 1,100 / 1,200 / 1,250 / 1,350

1,000 / 1,100 / 1,200 / 1,500 / 1,600

337

400

Topology

Online double conversion

Parallel system capacity

Up to 4 UPS systems via RPA Decentralized Architecture Up to 25% more flexibility on cable length in case of RPA system.

Static Bypass Inductor (Standard)

Cable entry Serviceability

Top or bottom

Front and top service access

HRG Ready

Yes

Input Connections

Single or Dual Feed

Short Circuit Withstand Rating

100 kAIC

Static Bypass Cabinet color

100% Rated – Continuous Duty

RAL 9005 (black)

Input Nominal input voltage

415 VAC, 3-ph, 4 W + ground

480 VAC, 3-ph, 3 W + ground

Voltage tolerance

-15% to +15%

Current distortion THDi

<3.0% 100% load normal mode – linear

Frequency range

60 Hz +/-10%

Power factor

0.99

Output Rated output voltage

415 VAC ph-ph, 240 VAC ph-n

480 VAC ph-ph

Static: +/-1% Dynamic (step load 0%-100%-0) Dynamic (step load 0%-50%-0)

Voltage tolerance

+/-3 +/-2

<3 @ 100% load-normal mode – linear <5 @ 100% load-normal mode – non-linear

Voltage distortion THDu

Frequency

60 Hz

Rated power factor

1.0

Efficiency Double conversion (VFI) eBoost Mode (VFD) Environment Protection rating Storage temperature Operating temperature Altitude without de-rating

Up to 97% Up to 99%

IP20

-13 to 131°F / -25 to 55°C 32 to 104°F / 0 to 40°C

Up to 1,000 m

1,500 m: -2.5% / 2,500 m: -2.5% 1,500 m: -2.5% / 1,500 m: -2.5%

Altitude with de-rating

Acoustic noise at 1 m

<80 dBA

Communications User interface

System graphical touch screen

Communication ports Customer interface

RS232, SNMP & Modbus

Remote shutdown, gen-set interface, external bypass contact

Batteries Types

Lithium ion, VRLA, Pure Lead, NiCd & Ni-Zn

Nominal Battery Bus

480V (240 Cell)

Standards Safety

ETL as tested to UL1778 / EN 62040-1 / UL9540

EMC

C3

Manufacturing

ISO 9001:2015, ISO 14001:2015, OHSAS18001

Weight, dimensions

415V systems

480V systems

1,000 kW 8,157 lbs / 3,700 kgs

1,000, 1,100 & 1,200 kW 8,157 lbs / 3,700 kgs 1,500 & 1,600 kW 9,039 lbs / 4,900 kgs

Weight [lbs] [kg]

1,100, 1,200, 1,250 & 1,350 kW 9,039 lbs / 4,900 kgs

Dimensions w x h x d (in) (mm) 129.92 x 86.61 x 39.37 (in) 3,300 x 2,200 x 1,000 (mm) Changes to the product or to the information contained in this brochure are reserved; so are errors and omissions. Please reference ABB order confirmations and submittal documentation packages for job specific configurations.

Download Technical Data Sheet for 415V for more information

Download Technical Data Sheet for 480V for more information

Made with FlippingBook Annual report maker