BuyLog Flippingbook JAN 2025
LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
8-168
— Power Break ™ II circuit breakers Trip unit selection How To Order 1. Determine the basic trip unit product number. 2. Select the trip unit suffix representing the protection function to complete trip unit product number. 3. Order rating plug separately. 4. For replacement trip units, replace “F” with “R”. Check empower for List Price and GO schedule.
Example: 1600 Ampere frame, 1000 ampere sensor, Long-time (L). Short-time (S), Instantaneous (I), RELT, Modbus Communications, EntelliGuard ™ with Advanced metering GB210L3X6XFXXXX. The replacement trip unit product number would be GB210L3X6XRXXXX. Rating Plug GTP1000U1025.
Power Break ™ II Trip Unit Suffix Power+ Trip Unit Suffix Selection Trip Unit Suffix 1 Trip Indicators Adjustable Instantaneous L/ST/I 1 GF 2 LI – –
Basic Trip Unit Selection
Enhanced MicroVersaTrip ™ Plus and MicroVersaTrip ™ PM Trip Units
Frame Size (Amperes)
Frame Rating (Amperes)
EntelliGuard ™ TU Trip Unit
Power+ ™ Trip Units
Sensor (Amperes)
Long-Time (L)
Short-Time (ST)
Inst. (l)
• • • • • •
• • • • •
–
200 400 800 800
GB102 GB105 GB108 GB108 GB210 GB316 GB320 GB310 GB420 GB425 GB530 GB740
D202 D204 D208 D208 D210 D216 D220 D210 D220 D325 D330 D440
B202 B204 B208 B208 B210 B216 B220 B210 B220 B325 B330 B440
• • – • •
LIT
– • – – •
–
800
800
LIT2
– • • •
LSI
1600
1000 1600 2000 1000 2000 2500 3000 4000
LSIT1
1600-2000
LSIT2 • 1 For high-range instantaneous or zone selective interlocking select MicroVersaTrip ™ Plus or PM trip units. 2 For ground fault-protection, select appropriate rating plug.
2000
2500
2500-3000
3000 4000
4000
EntelliGuard ™ TU with Selectable Phase Ammeter - Trip Indicators Standard
Switchable Short-Time (ST)
Long-Time with Fuse Settings (J)
Selectable Phase Ammeter
Inst (I)
Ground Fault (G)
Ground Fault Alarm (GA)
GF/ST Zone Interlock (ZSI) 3
Long-Time (L)
Overcurrent Protections
Trip Indicators
Suffix 1 1
• • • •
• • • •
• • • •
• • • •
• • • •
L3** L4** L5** L8**
LSI (S, switchable) LSIG (S, switchable) LSIGA (S, switchable)
opt. opt. opt. opt.
•
• • •
•
LSIGDA (GF/S, switchable) 2
1 Add suffix to basic trip unit to product number. 2 Defeatable/Switchable Ground Fault, not UL Listed.
MicroVersaTrip ™ Plus with Selectable Phase Ammeter—Trip Indicators Standard
Trip Unit Suffix 3
Trip Indicators
Selectable Phase Ammeter
Long-Time (L)
Short-Time (ST)
Inst (I)
High Inst. (H)
Ground Fault (G) 4
GF Zone Interlock (Z1) 5
GF/ST Zone Interlock (Z2) 5
Adjustable Instantaneous LI
• • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • •
• •
LIG
•
LIG Z1
• • • • • • • •
LSI
• • •
LSIG
•
LSIGZ1 LSIGZ2
•
Fixed High Range Instantaneous 4 LSH •
• • • •
• • •
• • •
LSHG
•
LSHGZ1 LSHGZ2
•
1 Add suffix to basic trip unit product number. 2 For single-phase 3 wire or 3-phase, 4-wire applications, order appropriate neutral current sensor separately, page 8-180. Defeatable Ground Fault (not UL Listed) is available. Use code GD in place of G. 3 Requires purchase of Zone Selective Interlock module(s) Type TIM1 (120 Vac control voltage). 4 Not available on 4000A stationary breaker frame.
Made with FlippingBook Ebook Creator