— ReliaMod™ Main breaker modules

Main breaker modules: 3-phase 4 wire 208Y/120Vac or 120/240V delta hi-leg, lugs included Main ampere rating kAIC Main breaker frame Breaker trip unit Wire entry Incoming lug sizes per phase & neutral (AWG/kcmil Cu/Al)

Service ground/ equipment ground (AWG/kcmil Cu/Al)

Ordering code RMM3BL4R RMM3BH4R RMM3BL6R RMM3BH6R RMM3BL8R RMM3BH8R RMM3BL10R 3 RMM3BH10R 3

400

65 XT5N 100 XT5S 65 XT5N 100 XT5S 65 XT6N 100 XT6S 65 XT7S 100 XT7H

TMA Top/Bottom

(2) 2/0 - 500

(2) #6-350

600

(2) 2/0 - 500

(2) #6-350

800

(3) 2/0 - 400

(2) #6-350

1000

Ekip Dip LS/I

(4) 4/0 - 500

(2) #6-350

(2) #6-350 RMM3BB12RCLL 1,2

1200

100

T8V PR332/P LSI

Bottom

Landing pad has provisions for double hole lugs up to (6) 750 kcmil Cu/Al. Lugs not included, to be provided by others.

65 XT7S 100 XT7H

Ekip Touch LSI Top/Bottom

(4) 4/0 - 500

RMM3BL12R 1,3 RMM3BH12R 1,3

(2) #6-350 RMM3BB14RCLL 1,2

1400

100

T8V PR332/P LSI

Bottom

Landing pad has provisions for double hole lugs up to (6) 750 kcmil Cu/Al. Lugs not included, to be provided by others.

— 800A MCB Module: RMM3BL8R

(4) 1/0 - 750 (6) 1/0 - 750 (4) 1/0 - 750 (6) 1/0 - 750

RMM3BB14R 1,5 RMM3BB14RL 1,4 RMM3BT14R 1,5 Coming soon 1,4

Top

(2) #6-350 RMM3BB16RCLL 1,2

1600

Bottom

Landing pad has provisions for double hole lugs up to (6) 750 kcmil Cu/Al. Lugs not included, to be provided by others.

(4) 1/0 - 750 (6) 1/0 - 750 (4) 1/0 - 750 (6) 1/0 - 750

RMM3BB16R 1,5 RMM3BB16RL 1,4 RMM3BT16R 1,5 Coming soon 1,4 Coming soon 1,2

Top

(2) #6-350

2000

Bottom

Landing pad has provisions for double hole lugs up to (6) 750 kcmil Cu/Al. Lugs not included, to be provided by others.

(6) 1/0 - 750 (6) 1/0 - 750

RMM3BB20RL 1,4

Top Coming soon 1 Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details. 1RELT included 2Lug landing pad only. Lugs not included, to be provided by others. 3 For larger 600-750 kcmil lugs on an XT7 frame main module, please order RXT7LUGKIT750. This kit will include mechanical lugs to accommodate (3) 500-750 kcmil Cu/Al cables per phase and neutral. 4 This main breaker module comes with (6) cable mechanical lugs per phase and neutral that accept (6) 1/0-750 kcmil Cu/AI cables. 5 This main breaker module comes with (4) cable mechanical lugs per phase and neutral that accept (4) 1/0-750 kcmil Cu/Al cables. This unit is more economical than a (6) cable lug model. However, please confirm these lugs meets your project requirements as there is no lug kit to change the lugs in the field once this item ships. If you require lugs that accept 5 or 6 cables per phase and neutral, please select the alternate version of this main module per footnote 4.

— 2000A MCB Module: RMM3BB20R