BuyLog Flippingbook FEB 2025

POWER CONDITIONING, BUYLOG SECTION 18

18-8

— PCS100 AVC-40 Technical specification

Utility – Input Power range

150 – 3600 kVA

Voltage (model specific) Nominal supply frequency

220 V – 480 V, 3-phase

50 Hz or 60 Hz

Load - Output Voltage

To match nominal input voltage

Displacement power factor

0 lagging to 0.9 leading

Efficiency

Typically >98%

Initial < 250 µs, complete < ½ cycle

Sag correction response

±1% typical, ±2% maximum

Voltage regulation accuracy

Sag correction accuracy Continuous regulation range Sag correction capability

±4%

±10%

40%

Overload capability

150% for 30 seconds, once every 500 seconds 125% for 10 minutes, 150% for 1 minute, 500% for 1 second, 2000% for 200 ms

Bypass overload capacity

Environmental Operating temperature range

0° C to 50° C 32° F to 122° F <75 dBA @ 2m

Noise

Enclosure rating

IP20

User interface User interface

10.1” color touch panel, multilingual

Touch panel

Full parameter control, system event log, voltage event log

Communication

Ethernet, Modbus TCP, E-mail

Standards and certifications Quality

ISO 9001 ISO 14001 CE, C-Tick IEC 62103

Environmental

Marking

Safety

Emissions: CISPR 11 Class A Group 1 Immunity: IEC 61000-6-2

Electromagnetic compatibility

Performance

IEC 61000-4-34

Made with FlippingBook Online newsletter creator