BuyLog Flippingbook AUG 2026

METERING, BUYLOG SECTION 2

2-21

— ReliaMod® modular metering Main pull box modules 1,2,3,4

MAIN PULL BOX MODULE: 1-PHASE 3 WIRE 120/240VAC (HORIZONTAL CROSS BUS NOT INCLUDED) Main ampere rating kAIC Wire entry Incoming line lugs per phase & neutral (AWG/kcmil Cu/Al) Outgoing load lugs per phase & neutral (AWG/kcmil Cu/Al) Enclosure

Ordering code

(1) 250-750 kcmil or (2) 3/0-250 kcmil

N3R Outdoor

400

100

Bottom

Landing pad has provisions for double hole lugs up to (1) 750 kcmil Cu/Al. Lugs not included, to be provided by others. Landing pad has provisions for double hole lugs up to (2) 750 kcmil Cu/Al. Lugs not included, to be provided by others. Landing pad has provisions for double hole lugs up to (3) 750 kcmil Cu/Al. Lugs not included, to be provided by others.

RMM1P4R

(2) 250-750 kcmil or (4) 3/0-250 kcmil

RMM1P8R

800

(4) 250-750 kcmil or (8) 3/0-250 kcmil

RMM1P12R

1200

400A Pull Box Module: RMM3P4R

MAIN PULL BOX MODULE: 3-PHASE 4 WIRE 208Y/120VAC OR 3-PHASE 4 WIRE 120/240VAC DELTA HI-LEG (HORIZONTAL CROSS BUS NOT INCLUDED) Main ampere rating kAIC Wire entry Incoming line lugs per phase & neutral (AWG/kcmil Cu/Al) Outgoing load lugs per phase & neutral (AWG/kcmil Cu/Al) Enclosure

Ordering code

(1) 250-750 kcmil or (2) 3/0-250 kcmil

N3R Outdoor

400

100

Bottom

Landing pad has provisions for double hole lugs up to (1) 750 kcmil Cu/Al. Lugs not included, to be provided by others. Landing pad has provisions for double hole lugs up to (2) 750 kcmil Cu/Al. Lugs not included, to be provided by others. Landing pad has provisions for double hole lugs up to (3) 750 kcmil Cu/Al. Lugs not included, to be provided by others.

RMM3P4R

(2) 250-750 kcmil or (4) 3/0-250 kcmil

RMM3P8R

800

(4) 250-750 kcmil or (8) 3/0-250 kcmil

RMM3P12R

1200

800A Pull Box Module: RMM3P8R

Main pull box module dimensions

MAIN PULL BOX MODULE: 1-PHASE 3 WIRE 120/240VAC Main ampere rating kAIC Wire entry W (in)

H (in) 43.17 50.46 54.59

D (in)

Ordering code

400 800

100

Bottom

16.80 24.86 32.98

7.70

RMM1P4R RMM1P8R RMM1P12R

11.32 11.32

1200

MAIN PULL BOX MODULE: 3-PHASE 4 WIRE 208Y/120VAC OR 3-PHASE 4 WIRE 120/240VAC DELTA HI-LEG (HORIZONTAL CROSS BUS NOT INCLUDED) Main ampere rating kAIC Wire entry W (in) H (in) D (in) Ordering code 400 100 Bottom 16.80 43.17 7.70 RMM3P4R 800 24.86 50.46 11.32 RMM3P8R 1200 32.98 54.59 11.32 RMM3P12R ¹ Pull boxes do not come with horizontal bussing to directly connect to a main section or meter stacks as they are for lug in, lug out applications. Pull boxes include a line side lug landing pad (lugs not included) and load side mechanical lugs. This can be useful for certain utilities that prefer to land their own cables in a separate enclosure and not directly on the line side of a main breaker. ² 400A and 800A pull box models conform to EUSERC drawings 343 and 347. The 1200A pull box models do not currently meet EUSERC requirements. ³ Limited to the lowest marked short circuit rating of the main and meter modules used. ⁴ Please click on any specific ReliaMod® ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details.

1200A Pull Box Module: RMM3P12R

Made with FlippingBook - Online Brochure Maker