LOW VOLTAGE POWER & INSULATED CASE CIRCUIT BREAKERS, BUYLOG SECTION 8
— SACE Emax 3 low voltage power circuit breakers Multi-standard version IEC 60947, UL1066 and CCC
Common data Rated maximum voltage
[V] [V]
635 600
Rated voltage
Test voltage (1min. 50/60 Hz)
[kV] [Hz]
2.2
Frequency
50 - 60
Number of poles
3-4
Version
Fixed (F) - Drawout (W)
Isolation behaviour
IEC 60947-2
Frame
E2.3
E4.3
E6.3
Performance levels
N-A S-A 1600 800
H-A V-A
S-A
H-A V-A
V-A
Rated uninterrupted current Iu @ 40°C
[A] [A] [A] [A] [A] [A] [A]
800
250
2500 2500 800
4000
2000 1200 1200 400
3000 3000 1600 5000 3200 3200 2000 6000 1
1600 1600 800 2000 2000 1200
2500 3000 3200
1600 2000
Neutral pole current-carrying capacity for 4-pole CBs
[%Iu]
100
100
100
100 100 100
100
100
100 100 100 100 100
50-100
Interrupting rating at rated maximum voltage
254 V 508 V 635 V
[kA] [kA] [kA] [kA]
50 50 50 50
65 65 65 65
85 85 85 85
65 65 65 65
85 85 85 85
100 100 100 100
85 85
Rated short time current (30 cycle/0.5s)
¹ 3-poles and draw out only - Overall dimension as 4 poles full size Note: Drawout versions utilize standard UL cradles/fixed parts
Dimensions and weight
E2.3
E4.3
E6.3
Dimensions H - Fixed/Drawout [in/mm] 14.61 [in] - 371 [mm]/ 16.73 [in] - 425 [mm]
14.61 [in] - 371 [mm]/ 16.73 [in]- 425 [mm] 10.63 [in]- 270 [mm]/ 15.47 [in]-393 [mm] 15.12[in] - 384 [mm]/ 20.08 [in]-510 [mm]
14.61 [in] - 371 [mm]/ 16.73 [in]- 425 [mm] 10.63 [in]- 270 [mm]/ 15.47 [in]-393 [mm] 30 [in]-762[mm]/ 34.96 [in] - 888 [mm]/ 39.92 [in] -1014 [mm] 31.61 [in] - 803[mm]/ 36.57 [in] - 929 [mm]/ 42.09 [in] - 1069 [mm]
D - Fixed/Drawout [in/mm] 10.63 [in] - 270 [mm]/ 15.47 [in]- 393 [mm]
W - Fixed 3p/4p
[in/mm] 10.87 [in] -276 [mm]/ 14.41 [in] -366 [mm]
W - Drawout 3p/4p [in/mm] 12.48 [in] - 317 [mm]/ 16.02 [in] -407 [mm]
16.73 [in] - 425/[mm]/ 21.69 [in] -551 [mm]
Weights (CB with trip unit/ current sensors/ standard accessories)
Fixed 3p/4p
[lbs/Kg] 115 [lbs] - 52 [kg]/ 148 [lbs] - 67 [kg]
Up to 2500A: 161[lbs] - 73 [kg]/ 203 [lbs] - 92 [kg]; 3200A: 201[lbs]-91 [kg]/256 [lbs] -116 [kg]; 3600A: 210 [lbs] - 95 [kg] Up to 2500A: 261 [lbs]-118 [kg]/ 325 [lbs] - 147 [kg]; 3200A: 300 [lbs]- 136 [kg]/ 377 [lbs] - 171 [kg]
314 [lbs]- 142 [kg]/360 [lbs]- 163 [kg]/406 [lbs] - 184 [kg]
Drawout 3p/4p including fixed part
[lbs/Kg] up to 1600A: 128 [lbs] -58 [kg]/ 150 [lbs] - 68 [Kg]; 2000A: 135 [lbs] - 61 [kg]/ 239 [lbs] - 108 [kg]
Up to 5000A: 486 [lbs]- 220 [kg]/554 [lbs]- 251 [kg]/ 620 [lbs] -281 [kg]
Electrical and mechanical life
FRAME
E1.3
E4.3
Mechanical life with regular ordinary maintenance prescribed by the manufacturer Electrical life with regular ordinary maintenance prescribed by the manufacturer
[Iu]
[A]
< 800 800 1200 1600 2000 <2500 2500 3200 5000 20 20 20 25 25 20 20 20 12 60 60 60 60 60 60 60 60 60
[No. cycles x 1000]
Frequency [Oper./Hour]
508 V 635 V
[No. cycles x 1000] [No. cycles x 1000]
8 8
8 8
7
12 10 10 8
7 7
3 2
6,5 10 8
10 8
Frequency [Oper./Hour]
30 30 30 30 30 20 20 20 10